Homepage Service Prices Webinars Instruction Videos HERS Rating Service Solar Rating Service Standards Energy Update FAQ
 

 

 1) New or Replacement Space Conditioning Systems

 2) Altered Space Conditioning Systems

 3) Duct Sealing and Testing

 4) Refrigerant Charge (RC) Verification

 5) Temperature Measure Access Holes (TMAH)

 6) Saturation Temperature Measurement Sensors (STMS)

 7) Charge Indicator Display (CID)

 8) Thermostatic Expansion Valves (TXV)

 9) Cooling Coil Airflow (CCA) Testing

10) Air Flow Measurement

11) Fan Watt Draw (FWD) Testing

  January 1, 2010  volume 1

Standards for HVAC Clarified

The new (2008) California Building Energy Efficiency Standards will go into effect on January 1, 2010. The new Standards make a distinction between two types of change-out situations

1) New or Replacement Space Conditioning Systems

 include a completely new or replacement duct system, and a new or replacement air handler unit.

 

2) Altered Space Conditioning Systems

Utilize the pre-existing duct system when installing or replacing some or all of the system components, such as the air handler unit, outdoor condensing unit, cooling or heating coil, or furnace heat exchanger.  The new Standards require that change-outs must be tested to ensure they meet the Home Energy Rating System (HERS) requirements in some climate zones as shown in the table below.  

 

3) Duct Sealing and Testing

 In Climate Zones 2 and 9-16 the duct sealing and testing rules that began in 2005 remain in effect. There are no changes to the allowable leakage rates or to which of the climate zones must meet the requirements. However, there is a change that eliminates the Table 8-3 “Alternatives to Duct Sealing” options from the Residential Compliance Manual. The Result is that installation of higher efficiency equipment is no longer an available alternative to meeting the HERS Duct Seal Test requirements.

 

4) Refrigerant Charge (RC) Verification

In Climate Zone 2 and 8-15, for Altered space conditioning systems and also for New or Replacement space conditioning systems, Refrigerant Charge Verification by third-Party HERS rater is required either for each unit or by sampling as is done in the current standard.

 

The installing contractor must measure the refrigerant charge, make any necessary corrections, then complete an Installation Certificate form that must be posted at the job site for use at final inspection. A third party HERS rater must also verify the RC. In order to achieve a valid RC Verification, the system must meet or exceed a minimum Cooling Coil Airflow (CCA) rate of 300 cfm per nominal ton of capacity by direct measurement or by the temperature split method. This airflow requirement is less stringent than airflow rate required for Cooling Coil Airflow and Fan Watt Draw Testing Described below.

 

If the system fails to meet the minimum airflow requirement, the HVAC contractor must modify the duct system or air handler  equipment in order to increase the system airflow.

 

Installers of New or Replacement space conditioning systems should consider reevaluating the duct system design prior to installation of the ducts (Using an industry recognized duct design method such as ACCA manual D) rather that simply replacing an old poorly designed duct system with "like for like" to end up with a brand new poorly designed duct system.  Installers of Altered space conditioning systems need to consider modification to the existing ducts to improve the airflow.  Modifications such as enlarging the return duct and return grille, may be sufficient.

 

Installers of New or Replacement space conditioning systems (with new duct systems) must install Saturation Temperature Measurement Sensors (STMS).  STMS make It is possible for HERS raters to verify RC without attaching gauges to the refrigerant lines. 

 

Installers of altered space conditioning systems do not have to install the STMS.  Both altered and new or replacement space conditioning systems require Temperature Measurement Access Holes (TMAH). A non-intrusive alternative to RC that is introduced by the new Energy Standards is the Charge Indicator Display (CID). If a CID is installed at the factory or in the field by the HVAC contractor, STMS and TMAH are not required.

 

5) Temperature Measurement Access Holes (TMAH)

TMAH are 5/16” holes that the installing contactor must drill – one in the supply plenum and one in the return plenum. The exact locations are specified in the Energy Commission document Reference Residential Appendices in section RA3.2. Watch for classes and training on installation of the TMAH. 

 

6) Saturation Temperature Measurement Sensors (STMS)

STMS are Type K thermocouples that are attached permanently – one to the evaporator coil and one to the condenser coil. The mini plug at the end of the thermocouple wire is plugged into a handheld digital thermometer to read the coil saturation temperature. This direct measurement of the temperature of the saturated region of the coil is an alternative to use of gauges for determining the coil saturation temperature readings needed for the refrigerant charge verification. The STMS may be installed at the factory or in the field by the HVAC contractor. Watch for classes and training on installation of the  STMS.  

 

7) Charge Indicator Display (CID)

CID is a new technology that is not yet commercially available, but when these devices become available, this will be a non-intrusive alternative to performing RC verification for the HERS rater. However the HVAC contractor will still need to perform RC verification at the time of the installation of the system. Watch for more information about the CID when it becomes available.


8) Thermostatic Expansion Valves (TXV)

TXV are no longer qualify for an automatic “pass” for HERS refrigerant charge verification. Systems with TXVs need to be tested for correct sub-cooling to verify refrigerant charge, and tested for superheat to ensure the TXVs are mounted and operating as designed.

 

9) Cooling Coil Airflow (CCA) and Fan Watt Draw (FWD)

FWD testing in Climate Zones 10-15,  new or replacement space conditioning systems (with new duct systems) must meet the CCA and FWD requirements. The airflow and watt draw measurements must be made simultaneously, and the results from the measurements are used to calculate a Watt per CFM value for the test result.

 

The air handler must deliver an air-flow of at least 350 CFM per nominal ton of capacity in order to pass, and the calculated result must be less than or equal to 0.58 Watts per CFM of measured airflow in order to pass the test. The installing contractor must measure the CCA and FWD, make any necessary corrections, then complete an Installation Certificate form that must be posted at the job site for use at final inspection. A third party HERS rater must also verify the CCA and FWD.

 

If the system fails to meet the minimum airflow, the HVAC contractor must modify the system ducts and/or air handler equipment in order to increase the system airflow.  Duct system improvements such as those mentioned above for meeting the minimum airflow for refrigerant charge verification are applicable to CCA and FWD.  Additionally, installation of a more efficient air handler unit may be a solution to meeting the required Watt per CFM.

 

In some situations (but not all) an air handler with a brushless permanent magnet motor might provide reduced fan Watt draw. If the problem is low air flow due to high static pressure, a higher efficiency motor by itself will probably not solve the problem. A good duct design, carefully installed, is highly recommended, and may be the lowest cost solution. Airflow measurement

 

10)  Air Flow Measurement   Air Flow Measurement Procedures are described in the Energy Commission document,  Reference Residential Appendices in section RA3.3. There are three acceptable methods:

               1) Flow Capture Hood at the return grille (s).

               2) Flow Grid Device at the return grille (s) or other point where all the fan airflow shall flow through the flow grid.

               3) Plenum Pressure Matching Procedure uses the same duct pressurization and Flow measurement device (fan flow-meter) as is used to measure

                   duct leakage. This procedure has been simplified for the new Standards to allow connection of the fan flow-meter at the return grille in the same way as

                   for the duct leakage test. This change makes it possible to test both the duct leakage and the airflow with the Same setup, which may be a time saver.

                   Watch for classes and training on this method.
 

11) Fan Watt Draw (FWD) Testing

 Fan Watt Draw  Measurement must be done with a true Power meter device that measures voltage and amperage simultaneously and reports the true power value. True power meters are available in both plug-in and clamp-on configurations. Voltage and amperage can be taken separately, but their product is Volt Amps or “Apparent Watt Draw.” True watt draw is the product of the voltage, amperage, AND power factor

 

A Certified California Title 24 Energy Code Compliance Service

CEA (Certified Energy Analyst)  Residential #R08-08-261  & Non-Residential #NR08-08-540

CEPE (Certified Energy Plans Examiner)  Residential #R08-07-1639   &  Non-Residential #NR08-07-3618